Class A extended support per latest 61000-4-30 revision. Many new parameters, averaged intervals, and more
-
Device Configuration FILE – Based on XML file. Under device CF. Enables user to manage configuration via files (BACKUP, MODIFY).
-
MODBUS-RTU, MODBUS-TCP and DNP3-
-
PQZIP Enhancements (User must change Record type in PQZIP Recording to PQSCADA 3.3)
-
Hierarchal folders: Folder for each year, month, day and hour. Now it is easier for manual downloading of files per desired time period.
-
Entire IO module ports recording: while in previous version only Digital inputs were recorded in PQZIP; now also Digital output, Relays, Analog Inputs, and Outputs.
-
VDC in PQZIP (G4500) is also supported.
-
For advanced users: There is a capability to modify sampling of G4430/G4500 and obtain in PQZIP either V=512, I=512 Samples/cyc (default is of course V=1024,I=256).
-
Customized User parameters
-
The user can add his/her own parameters to PQZIP (up to 32 different parameters.
-
Usage: The user writes values via MODBUS registers and these registers are being continuously recorded as part of PQZIP and viewable in the PQS/INV in parallel to the power parameters for easier investigation.
-
WEB interface enhancements and improvements
-
Advanced Supervision Reset- for External Modem/Router; an advanced user feature, (configurable via Telnet only). This feature enables the device to RESET (turn power OFF/ON) an external modem/router in case it detects no-connectivity. This feature prevents remote communication stack in case the modem software is stacked. The reset function is configurable to pulse supply voltage either via POE (LCD ETH PORT), or DO/RELAY ports of MULTI-IO Extension card.
-
POE powering new HW module - [POE to 5V/12V Supply box] that can operate external modems requiring 5 or 12V.
-
Compliance extensions
-
Compliance is now always running.
-
Compliance Customized Configuration is now supported for Events Hysteresis, as well as configurable discard or no-discarding of intervals during flagging.
Upgrading the Firmware Video Demonstration

Monitoring IEC 61000-4-30 Video Demonstration
All new BLACKBOX devices will now be supplied with these latest versions.